INTRODUCTION

The AP600 makes all the required power measurements for three phase generating or consuming electrical equipment. It is an entirely solid state system with no moving parts, and uses a microprocessor to measure voltage, current, and frequency, and calculate power consumption and power factor in real time. The measurements are displayed in large, bright red LEDs. The AP600 can be used in many applications such as:

a. Generator set output panel.

b. Load bank input monitor.

c. Industrial power supply monitor for machinery lines, industrial heating and other processes which consume electrical energy.

 

SPECIFICATIONS

Input voltage 0 to 350 V AC RMS, accuracy 1%
Input current 0 to 5 A AC RMS, accuracy 1%
Display frequency range 33.4 to 66.7 Hz, accuracy 0.1% when voltage is above 160V
Current ranges (Amps) 40.00 50.00 60.00 75.00
  80.00 100.0 125.0 150.0
200.0 250.0 300.0 400.0
500.0 600.0 750.0 800.0
1000 1200 1400 1500
1600 2000 2500 3000
3500 4000 5000 6000
System power supply 190 to 350 V AC 50/60 Hz
System power consumption 5 W typical
Ambient temperature 0 - 60°C
Ambient humidity 10 - 90% non-condensing

 

 

 


Copyright © 2001 - Advanced Power Pty Limited